Alarm, fault and system messages
12.2 Diagnostics
SIPART PS2 with PROFIBUS communication
228
Operating Instructions, 09/2007, A5E00127926-07
17 ZERO - zero point displacement
Display of the current displacement of the lower hard end stop with respect to its initialization
value. The activation of the "down tight closing function" is a condition to determine this.
Activate using the "YCLS" parameter in the configuration menu. If the underlying function is
deactivated in the configuration menu, "OFF" is displayed.
18 OPEN - displacement of upper end stop
Display of the current displacement of the upper hard end stop with respect to its initialization
value. The activation of the "up tight closing function" is a condition to determine this.
Activate using the "YCLS" parameter in the configuration menu. If the underlying function is
deactivated in the configuration menu, "OFF" is displayed.
19 PAVG - position average
The last calculated comparison average is displayed here. The following status messages
are also available:
●
OFF
The underlying function is deactivated in the configuration menu.
●
IdLE (inactive)
The function has not been started yet.
●
rEF (the reference average is calculated)
The function was started, and the reference interval is in progress at the moment.
●
COMP (the comparison average is calculated)
The function was started, and the comparison interval is in progress at the moment.
20 P0 - potentiometer value of the lower end stop
21 P100 - potentiometer value of the upper end stop
Both these values indicate the measured values of the position displacement sensor
(potentiometer) on the lower or upper hard end stop, as they were determined during
automatic initialization. The values of manually approached end positions are applicable for
manual initialization.
22 IMPUP - impulse length up
This parameter can be set for special applications.
23 IMPDN - impulse length down
The smallest impulse lengths that can be used to move the actuator are determined during
the initialization process. They are separately determined for the "Up" and "Down" directions
and displayed here.
This parameter can be set for special applications.