Parameter assignment/Addressing
10.1 Overview of the parameters
SIPART PS2 with PROFIBUS communication
Operating Instructions, 09/2007, A5E00127926-07
139
Overview of the positioner parameters 6 to 53
Parameter
Function
Parameter values
Unit
Device operating mode (ID No.)
Independent of manufacturer
0
53.IDENT
Full functionality
1
1)
Setpoint turning points only appear when "9.SFCT = FrEE" is selected.
Normally closed
contact means:
Operation when a switch is open or Low level
2)
Normally open contact
means:
Operation when a switch is closed or High level
Normal means:
High level: no fault message
3)
Inverse means:
Low level: no fault message
4)
"+" means:
OR logic combination
5)
Preset effects "NOINI"!
10.1.3
Overview parameters A to P
Introduction
These parameters are used to set the extended diagnostic functions of the positioner.
Note
Factory-set parameter values are printed in bold in the following table.
Note
Display
Parameters A to P and their sub-parameters are only displayed when the extended
diagnostics has been activated using parameter "XDIAG" with parameter value "On1", "On2"
or "On3".
Overview parameter A
Parameter
Function
Parameter values
Unit
A. PST
Partial stroke test with the following parameters:
A1.STPOS Starting position
0.0 ... 100.0
%
A2.STTOL
Starting tolerance
0.1 ... 2.0 ... 10.0
%
A3.STEP
Step height
0.1 ... 10.0 ... 100.0
%
A4.STEPD Step direction
uP / do / uP do