Parameter assignment/Addressing
10.1 Overview of the parameters
SIPART PS2 with PROFIBUS communication
Operating Instructions, 09/2007, A5E00127926-07
141
Overview parameter F
Parameter
Function
Parameter values
Unit
F. ZERO
Zero point monitoring with the following parameters:
F1.LEVEL1 Threshold 1
0.1 ... 1.0 ... 10.0
F2.LEVEL2 Threshold 2
0.1 ... 2.0 ... 10.0
F3.LEVEL3 Threshold 3
0.1 ... 4.0 ... 10.0
%
Overview parameter G
Parameter
Function
Parameter values
Unit
G. OPEN
Displacement of the upper stop with the following parameters:
G1.LEVEL1 Threshold 1
0.1 ... 1.0 ... 10.0
G2.LEVEL2 Threshold 2
0.1 ... 2.0 ... 10.0
G3.LEVEL3 Threshold 3
0.1 ... 4.0 ... 10.0
%
Overview parameter H
Parameter
Function
Parameter values
Unit
H. TMIN
Monitoring of the lower limit temperature with the following parameters:
H1.TUNIT
Temperature unit
°C
°F
H2.LEVEL1 Threshold 1
-40 ... -25 ... 90
-40 ... 194
H3.LEVEL2 Threshold 2
-40 ... -30 ... 90
-40 ... 194
H4.LEVEL3 Threshold 3
-40 ... 90
-40 ... 194
°C/°F
Overview parameter J
Parameter
Function
Parameter values
Unit
J. TMAX
Monitoring of the upper limit temperature with the following parameters:
J1.TUNIT
Temperature unit
°C
°F
J2.LEVEL1 Threshold 1
-40 ... 75 ... 90
-40 ... 194
J3.LEVEL2 Threshold 2
-40 ... 80 ... 90
-40 ... 194
J4.LEVEL3 Threshold 3
-40 ... 90
-40 ... 194
°C/°F
Overview parameter L
Parameter
Function
Parameter values
Unit
L. STRK
Monitoring the path integral with the following parameters:
L1. LIMIT
Limit for the number of changes of direction
1 ... 1E6 ... 1E8
L2.FACT1
Factor 1
0.1 ... 1.0 ... 40.0
L3.FACT2
Factor 2
0.1 ... 2.0 ... 40.0