Parameter assignment/Addressing
10.1 Overview of the parameters
SIPART PS2 with PROFIBUS communication
Operating Instructions, 09/2007, A5E00127926-07
137
Overview of the positioner parameters 6 to 53
Parameter
Function
Parameter values
Unit
33 : 1
n1 - 33
50 : 1
n1 - 50
Freely adjustable
FrEE
10.SL0 ...
30.SL20
1)
Setpoint turning points with free characteristic
10.SL0
0%
11.SL1 ....
5% ...
29.SL19
95%
30.SL20
at
100%
0 ... 100.0
%
31.DEBA
Controller dead zone
Auto / 0.1 ... 10.0
%
32.YA
Beginning of manipulated variable limiting
0.0 ... 100.0
%
33.YE
End of manipulated variable limiting
0.0 ... 100.0
%
Standardization of manipulated variable
To mechanical travel
MPOS
34.YNRM
At flow
FLOW
Tight closing with manipulated variable
None
no
Above only
uP
Below only
do
35.YCLS
Above and below
uP do
36.YCDO
Value for tight closing below
0.0 ... 100
%
37.YCUP
Value for tight closing above
0.0 ... 100
%
Function of the BE1
Normally open contact
Normally closed
contact
None
OFF
Message only
on
-on
Block configuring
bloc1
Block configuring and manual
operation
bloc2
Move valve to position YE
uP
-uP
Move valve to position YA
doWn
-doWn
Block movement
StoP
-StoP
38.BIN1
2)
Partial stroke test
PST
-PST
Function of the BE2
Normally open contact
Normally closed
contact
None
OFF
Message only
on
-on
Move valve to position YE
uP
-uP
Move valve to position YA
doWn
-doWn
Block movement
StoP
-StoP
39.BIN2
2)
Partial-Stroke-Test
PST
-PST