Commissioning
9.4 Commissioning the part-turn actuators
SIPART PS2 with PROFIBUS communication
Operating Instructions, 09/2007, A5E00127926-07
131
3.
The displayed potentiometer position is within the permissible range between "P5.0" and
"P95.0".
NOTICE
Setting of the adjustment angle
The usual adjustment angle for part-turn actuators is 90°. Accordingly set the
transmission ratio selector in the positioner to 90°.
Initializing the positioner manually
1.
Switch to the "Configuration" mode. Keep the operating modes button pressed for
more than 5 s. The following is shown on the digital display:
2.
Set the "YFCT" parameter to "turn". Press the decrement button for this purpose. The
following is shown on the digital display:
3.
Call the second parameter "YAGL". Press the operating mode button for a short while
for this purpose. The following is shown on the digital display:
4.
Call the "INITM" parameter. Press the operating mode button twice for this purpose.
The following is shown on the digital display:
5.
Start the initialization process. Keep the increment button pressed for more than 5 s
until the following is shown on the digital display:
6.
The current potentiometer position is shown on the digital display after 5 s. Examples of
the displayed potentiometer positions are given below: