Parameter assignment/Addressing
10.2 Description of parameters
SIPART PS2 with PROFIBUS communication
Operating Instructions, 09/2007, A5E00127926-07
157
Figure 10-4 Display of a threshold 3 fault message
The factory setting is "OFF".
See also
Description of parameter A (Page 159)
XDIAG parameter (Page 231)
10.2.2.19
Description of parameter 49
49.FSTY - safety position
Use this parameter to move the actuator to a defined safety position when communication
fails. Three settings are available:
●
FSVL:
the actuator is controlled using the parameterized safety setpoint. This value also
becomes effective after a power failure.
●
FSSP:
the actuator is controlled using the last effective setpoint.
●
FSAC:
the exhaust air valve is opened. The single-acting actuator moves to the end position due
to its spring force.
The factory setting is "FSAC".
10.2.2.20
Description of parameter 50
50.FSTI - monitoring time to set the safety position
If communication fails, the positioner switches to the safety position after the set value
expires.
The factory setting is "0".