Functional safety
8.2 Device-specific safety notes
SIPART PS2 with PROFIBUS communication
114
Operating Instructions, 09/2007, A5E00127926-07
●
The connected valve actuator must be single acting and switch the valve to its safe end
position by spring force in the following cases:
–
Pressure failure
–
At a chamber pressure (Y1 connection) up to a third of the maximum available inlet
pressure (Pz connection)
●
The air outlet does not contain any additional cross-sectional contractions leading to an
increased dynamic pressure. In particular, a silencer is only allowed if icing or other
contamination is ruled out.
●
The restrictor in the Y1 circuit may not be completely closed during operation.
●
The auxiliary pneumatic power is free of oil, water and dirt in line with:
DIN/ISO 8573-1, maximum class 2
●
The average temperature viewed over a long period is 40 °C.
●
The MTTR after a device fault is 8 hours.
●
In case of a fault, the pneumatic outlet of the positioner is depressurized. A spring in the
pneumatic drive must move the valve to the pre-defined, safe end position.
●
A dangerous failure of the positioner is when the pressure outlet is not depressurized, or
the safety position is not reached, when the LOW signal is less than 4.5 V at the input for
the safety shutdown.