Commissioning
9.3 Commissioning the linear actuators
SIPART PS2 with PROFIBUS communication
Operating Instructions, 09/2007, A5E00127926-07
125
Setting parameter 3
Proceed as follows to set parameter 3:
1.
On the scale of the lever, read the value marked by the carrier pin.
2.
Set the parameter to the read value. Use the increment or decrement buttons for
this purpose.
Aborting the automatic initialization process
1.
Press the operating mode button. The following is shown on the digital display:
2.
Exit the "Configuration" mode. Keep the operating modes button pressed for more
than 5 s.
3.
The software status is displayed.
4.
After releasing the operating mode button, the positioner is in the "P manual mode",
i.e. the positioner has not been initialized.
9.3.3
Manual initialization of linear actuators
You can use this function to initialize the positioner without needing to move the actuator to
the end stops. The start and end positions of the actuator travel are set manually. When the
control parameters are optimized, the further initialization process runs automatically.
Conditions
The following conditions must be fulfilled before activating the manual initialization:
1.
The positioner has been prepared for using on linear actuators.
2.
The actuator spindle can be moved completely.
3.
The displayed potentiometer position is within the permissible range between "P5.0" and
"P95.0".
Initializing the positioner manually
1.
Switch to the "Configuration" mode. Keep the operating modes button pressed for
more than 5 s. The following is shown on the digital display: