Parameter assignment/Addressing
10.2 Description of parameters
SIPART PS2 with PROFIBUS communication
Operating Instructions, 09/2007, A5E00127926-07
171
2.
Set the suitable parameter values in sub-parameters. The setting options available in
sub-parameters are described below.
The positioner generates a fault message if the upper limit temperature exceeds a threshold
during the test.
The factory setting is "OFF".
J1.TUNIT - temperature unit
Use this sub-parameter to set the temperature unit "°C" or "°F". The selected temperature
unit is then also applicable for all other temperature-based parameters.
The factory setting is "°C".
J2.LEVL1 - threshold 1
Use this sub-parameter to set a threshold in "°C" or "°F". Use threshold 1 to monitor the
upper limit temperature. Set the threshold in a range from "-40.0C" to "90.0C" or "-40.0F" to
"194.0F".
The positioner triggers a fault message if the current temperature inside the enclosure
exceeds threshold 1. The process to activate and display this fault message is described in
the "XDIAG" parameter.
The factory setting is "75.0C".
J3.LEVL2 - threshold 2
Use this sub-parameter to set a threshold in "°C" or "°F". Use threshold 2 to monitor the
upper limit temperature. Set the threshold in a range from "-40.0C" to "90.0C" or "-40.0F" to
"194.0F".
The positioner triggers a fault message if the current temperature inside the enclosure
exceeds threshold 2. The process to activate and display this fault message is described in
the "XDIAG" parameter.
The factory setting is "80.0C".
J4.LEVL3 - threshold 3
Use this sub-parameter to set a threshold in "°C" or "°F". Use threshold 3 to monitor the
upper limit temperature. Set the threshold in a range from "-40.0C" to "90.0C" or "-40.0F" to
"194.0F".
The positioner triggers a fault message if the current temperature inside the enclosure
exceeds threshold 3. The process to activate and display this fault message is described in
the "XDIAG" parameter.
The factory setting is "90.0C".