Functions/operations using PROFIBUS PA
11.3 Cyclic data transfer
SIPART PS2 with PROFIBUS communication
Operating Instructions, 09/2007, A5E00127926-07
207
Process-dependant:
P
PROCESS RELATED
Functional check:
F
FUNCTION CHECK
Collective diagnostics messages
Collective diagnostics messages in the case of the activated condensed status are shown in
the following table:
Byte
Bit Name and meaning
Cause
Measure
Group
Power was fed to the device.
Or:
SIMATIC PDM was used to
trigger a warm restart,
0
0
... 7
Reserved
Or:
The internal watchdog has
responded.
-
-
0
... 2
Reserved
The device was reset to factory
settings.
-
-
3
DIA_WARMSTART
Warm restart executed (goes to "0"
after 10 s)
To determine the cause, check
in DIAGNOSTICS_EXTENSION
and
DIAGNOSTICS_EXTENSION_2
which diagnostics event has
triggered the message.
Check the cabling
and the supply
unit.
-
4
DIA_COLDSTART
Restart executed
(goes to "0" after 10 s)
-
-
-
5
DIA_MAINTENANCE
Maintenance required
You have changed the
PROFIBUS identification number
parameter during the active
cyclic operation. The device
reports the identification number
violation and displays a failure
warning. In case of a warm
restart, the device will no longer
participate in the cyclic transfer
of useful data without changing
the system configuration.
Depends on the
triggering
diagnostics event.
M1, M12,
M
1
6
Reserved
-
-
-