Alarm, fault and system messages
12.1 Representation of system messages on the digital display
SIPART PS2 with PROFIBUS communication
222
Operating Instructions, 09/2007, A5E00127926-07
Line
Operating mode
MAnn
X
Manual mode
(nn = setpoint)
•
Switch to the
automatic mode
using the
operating mode
button
LO nn
X
X
Positioner is in the "local
override mode"
•
Set the target
mode with class 2
master to
"Automatic"
•
Send the "0x80"
status (good)
OS --
X
X
X
Positioner is in the "out of
service mode"
•
Set the target
mode with class 2
master to
"Automatic"
•
Send the "0x80"
status (good)
Display range was
exceeded.
Possible causes:
oFL /
127.9
•
Friction clutch or
•
Transmission ratio
selector were moved
or
•
The positioner was
attached to another
actuator without re-
initializing it
•
Move the friction
clutch such that
the actual value
display remains
within 0.0 to 100.0
when moving the
actuator or
•
Adjust the
transmission ratio
selector or
•
Set the factory
setting (preset)
and execute the
initialization
process
EXSTP
X
X
Actuator was stopped
using a binary input
EX UP
X
X
Actuator is moved to the
upper end stop using a
binary input
EXDWN
X
X
Actuator is moved to the
lower end stop using a
binary input
EXTPSt
The partial stroke test was
activated, e.g. using a
binary input
inPSt
Cyclic
partial stroke test