Par. No.
Name
Range
Default
Unit
P0610
Motor I
2
t reaction
0 - 2
1
--
Defines reaction when motor I
2
t reaches warning threshold.
Possible settings:
0
Warning, no reaction, no trip
1
Warning, Imax reduction, trip F0011
2
Warning, no reaction, trip F0011
Dependency:
See parameter P0611.
Note:
Default value depends on connection macro selected. See Table 7-11 for details
P0611
Motor I
2
t time constant
0 - 16000
Depends on
inverter type
s
Thermal time constant for the motor.
Dependency:
P0611 < 99 s: I
2
T-calculation inactive
To activate I
2
T calculation, set P0611 to a value > 99 s.
Note:
The value of P0611 is estimated according to the motor data during quick commissioning. When the
calculation of motor parameters during quick commissioning is complete, the stored value can be replaced
by the value given by the motor manufacturer.
P0640
Motor overload factor [%]
10.0 - 400.0
110.0
%
Defines motor overload current limit in [%] relative to P0305 (rated motor current).
P0701
Function of digital input 1
0 - 99
0
--
Selects function of digital input 1.
Possible settings:
0
Digital input disabled
1
ON/OFF 1
2
ON reverse/OFF1
3
OFF2 - coast to standstill
4
OFF3 - quick ramp down
9
Fault acknowledge
10
JOG right
11
JOG left
12
Reverse
13
MOP up (increase frequency)
14
MOP down (decrease frequency)
15
Fixed setpoint (direct selection)
16
Fixed setpoint (direct sel ON)
99
Enable value 722.0 set in other parameters.
Note:
Default value depends on connection macro selected. See Table 7-11 for details
Parameter list
SINAMICS V10
84
Operating Instructions, 08/2011, A5E03453178 (this is not an order number)