DIP-switch (AO): Depends on external RPM Meter
DIP-switch (AI): Must be set to voltage (V) mode
Table 6-3
Select connection macro C03 with the operator panel after the wiring (please refer to
"Operation mode
②
- Connection macro selection", and then below parameter settings
will be automatically finished.)
Par. No. Parameter name
Range
Unit
Default
r0007
Selected connection macro and application macro
C0100 - C1105
- -
C03xx*
P0610
Motor I
2
t reaction
0 - 2
- -
2
P0701
Function of digital input 1
0 - 99
- -
1
P0702
Function of digital input 2
0 - 99
- -
0
P0703
Function of digital input 3
0 - 99
- -
0
P1000
Selection of frequency setpoint
0 - 53
- -
2
P0725
PNP/NPN digital inputs
0 - 1
- -
1
* "xx" means current application macro.
Commissioning
6.1 Typical connection modes
SINAMICS V10
44