Table 6-10
Select connection macro C10 with the operator panel after the wiring (please refer to
"Operation mode
②
- Connection macro selection", and then below parameter settings
will be automatically finished.)
Par. No. Parameter name
Range
Unit
Default
r0007
Selected connection macro and application macro
C0100 - C1105
- -
C10xx*
P0610
Motor I
2
t reaction
0 - 2
- -
2
P0701
Function of digital input 1
0 - 99
- -
1
P0702
Function of digital input 2
0 - 99
- -
13
P0703
Function of digital input 3
0 - 99
- -
14
P1000
Selection of frequency setpoint
0 - 53
- -
1
P0725
PNP/NPN digital inputs
0 - 1
- -
1
* "xx" means current application macro.
NOTICE
The PI controller function is valid only in this connection mode and when the current control
mode is set to REM mode.
In this connection mode, PI setpoint must be set via P2240 and feedback value shall,
depending on actually connected sensor, be scaled via P0753 to P0761.
Besides parameters listed in Auto hotspot , P2280 (default value: 0.500), P2285 (default
value: 10.000s) and P2293 (default value: 10.00s) are also related to connection mode.
Commissioning
6.1 Typical connection modes
SINAMICS V10
54
Operating Instructions, 08/2011, A5E03453178 (this is not an order number)