5.5
Connecting cabinets
DANGER
Danger due to failure of the protective and monitoring equipment
The converter must be grounded to ensure that it operates safely and reliably. If the converter
is operated with insufficient grounding, then the protection and monitoring functions can fail.
Death, serious injury, or material damage will result.
● Always apply all of the necessary protective measures.
● Always observe the five safety rules when working with the converter.
● Follow these steps when grounding the machine:
– Establish the connections in a cabinet.
– Ensure that the connections are also established over several cabinets.
– Establish the ground connection for the whole plant immediately.
If several cabinets are set up as one unit, the grounding connections of the individual cabinets
must be connected with each other. A grounding lug connection cable is supplied with each
cabinet. To connect the ground connections for several cabinets, proceed as follows:
1. Insert the grounding cable through the cabinet side panel.
2. Fasten the grounding cable to the grounding lug using an M10 screw.
3. Tighten the screw with a torque of 25 Nm.
Assembly
5.5 Connecting cabinets
SINAMICS PERFECT HARMONY GH150 6SL3826
70
Operating Instructions 05/2020
Summary of Contents for SINAMICS PERFECT HARMONY GH150 6SL3826
Page 2: ...19 06 2020 09 25 V14 00 ...
Page 120: ...Spare parts SINAMICS PERFECT HARMONY GH150 6SL3826 120 Operating Instructions 05 2020 ...
Page 124: ...Service Support SINAMICS PERFECT HARMONY GH150 6SL3826 124 Operating Instructions 05 2020 ...
Page 130: ...Quality documents SINAMICS PERFECT HARMONY GH150 6SL3826 130 Operating Instructions 05 2020 ...
Page 135: ......