Installing the current transformer
To install the current transformer, proceed as follows:
1. Carry out the removal steps in reverse order.
2. Screw the screws into the busbars with a tightening torque of 25 Nm.
3. After installing the current transformer, check that it works properly.
9.7.5
Replacing the precharging transformer
WARNING
Danger to life as a result of incorrect replacing the precharging transformer
Replacing the precharging transformer incorrectly can result in death, serious injury, or
material damage.
● Follow "the five safety rules (Page 13)".
● Before replacing the precharging transformer, open the safety disconnector for the 400 V
supply.
● The transformer is heavy, therefore lift it carefully:
– Version with 10 kV and 13.8 kV: 50 kg
– Version with 6.9 kV and 4.16 kV: 35 kg
Installing the precharging transformer
1. Remove the paint from at least one screw position on the base brackets. This is where the
transformer will be grounded.
2. Install the new transformer in the reverse order to when you removed it. Comply with the
specified torque (Page 104) of the fastening screws. When attaching the connecting cables
ensure that the cables do not twist.
3. Check that the precharger is working correctly.
Maintenance
9.7 Repair
SINAMICS PERFECT HARMONY GH150 6SL3826
108
Operating Instructions 05/2020
Summary of Contents for SINAMICS PERFECT HARMONY GH150 6SL3826
Page 2: ...19 06 2020 09 25 V14 00 ...
Page 120: ...Spare parts SINAMICS PERFECT HARMONY GH150 6SL3826 120 Operating Instructions 05 2020 ...
Page 124: ...Service Support SINAMICS PERFECT HARMONY GH150 6SL3826 124 Operating Instructions 05 2020 ...
Page 130: ...Quality documents SINAMICS PERFECT HARMONY GH150 6SL3826 130 Operating Instructions 05 2020 ...
Page 135: ......