LED
Color
Status
Description; cause
Remedy
RUN /
ERR
-
Off
The electronic power supply is missing or
lies outside the permissible tolerance
range.
-
Green
Continuous
light
The component is ready for operation
and cyclic DRIVE-CLiQ communication
is in progress.
-
Orange
Continuous
light
DRIVE-CLiQ communication is being es‐
tablished.
-
Red
Continuous
light
At least one fault is present in the com‐
ponent.
LED is controlled irrespective of the cor‐
responding messages being reconfig‐
ured.
Remedy and acknowledge fault.
Green/red
0.5 Hz flashing
light
Firmware download in progress.
-
2 Hz flashing
light
Firmware download is complete. Waiting
for POWER ON.
Carry out a POWER ON.
Green/
orange
or
Red/orange
Flashing light
Component recognition via LED is acti‐
vated.
The color depends on the LED state
when component recognition is activated.
-
8.4.2.2
LEDs of the SIRIUS safety relay
Table 8-2
LEDs of the SIRIUS safety relay
LED
Operation
Channel 1
Channel 2
Line supply
EMERGENCY STOP
Enabling circuits
ON
ON
ON
Not actuated
Closed
ON
OFF
Actuated
Open
Fault
ON
OFF
● Relay jammed
● Motor contactor jammed
● Defect in electronics
Open
ON
OFF
Cross-circuit fault or ground fault in the EMER‐
GENCY STOP circuit
Operation
8.4 Fault and system messages
SINAMICS PERFECT HARMONY GH150 6SL3826
90
Operating Instructions 05/2020
Summary of Contents for SINAMICS PERFECT HARMONY GH150 6SL3826
Page 2: ...19 06 2020 09 25 V14 00 ...
Page 120: ...Spare parts SINAMICS PERFECT HARMONY GH150 6SL3826 120 Operating Instructions 05 2020 ...
Page 124: ...Service Support SINAMICS PERFECT HARMONY GH150 6SL3826 124 Operating Instructions 05 2020 ...
Page 130: ...Quality documents SINAMICS PERFECT HARMONY GH150 6SL3826 130 Operating Instructions 05 2020 ...