Preparations for use
4
When carrying out any work, carefully observe the information provided in Chapter "Safety
4.1
Requirements for installation location
The cabinet units are designed to be installed in general equipment rooms and areas according
to IEC 62103, degree of pollution 2, without conductive pollution. For this reason, SINAMICS
devices must be protected in such a way that they cannot be touched directly when they are
being installed in general operating areas.
The operating areas must be dry and free of dust. The air supplied must not contain any
electrically conductive gas, vapors, or dust which could impair operation.
For information about permissible ambient and installation conditions, see the "Technical data
and drawings" section.
4.2
Inspections when the equipment is received
4.2.1
Checking shock and tilt indicators
The purpose of shock and tilt indicators
The unit is equipped with shock and tilt indicators to monitor for damage during transit.
Carefully check the shock and tilt indicators before commissioning the device.
WARNING
Danger to life as a result of unsafe operation
Safe operation of the device is not guaranteed if the shock or tilt indicator has tripped
(responded)
This can result in death, serious injury or material damage.
● If one of the indicators has tripped, do not perform any commissioning.
● Inform the Technical Support. Only specialist Siemens technicians can recommend
appropriate measures.
SINAMICS PERFECT HARMONY GH150 6SL3826
Operating Instructions 05/2020
57
Summary of Contents for SINAMICS PERFECT HARMONY GH150 6SL3826
Page 2: ...19 06 2020 09 25 V14 00 ...
Page 120: ...Spare parts SINAMICS PERFECT HARMONY GH150 6SL3826 120 Operating Instructions 05 2020 ...
Page 124: ...Service Support SINAMICS PERFECT HARMONY GH150 6SL3826 124 Operating Instructions 05 2020 ...
Page 130: ...Quality documents SINAMICS PERFECT HARMONY GH150 6SL3826 130 Operating Instructions 05 2020 ...
Page 135: ......