● Attach the cable shield to a shield busbar directly after the line inlet into the cabinet. Insulate
the shielded cable without any interruptions. Route the cable shield up to the device
connection.
①
Shield busbar
②
Shielded cable
③
Mounting clip
Figure 6-1
Shield connection using a clip
NOTICE
Impaired functionality as a result of damaged or incorrectly connected cable shields
Incorrect connection or damaging of the cable shield can impair the function of the system.
● Handle the cable shield carefully.
● Ensure that the cable shield is correctly connected.
● Bridge shield gaps (at terminals, circuit-breakers, contactors, etc.) with minimum
impedance and through the largest possible surface area.
①
Shield busbars
②
Cables
③
Terminals
Figure 6-2
Bridging shield gaps
Electrical connection
6.2 Electromagnetic compatibility
SINAMICS PERFECT HARMONY GH150 6SL3826
Operating Instructions 05/2020