WARNING
Burns caused by inadequate cable insulation
Improperly laid or damaged cables and incorrectly attached cable shieldings can heat up in
places and cause fires or short-circuits wherever they make contact.
● Check whether all the cable shields are intact.
● Insulate damaged cable shields.
● Make sure that a short-circuit cannot occur on the power cables due to failure of the
insulation as a result of incorrect cable installation.
NOTICE
Damage if the auxiliary power supply is not available
When the auxiliary power supply is switched off, data about error message statuses can be
lost. Inadequate diagnostic and error rectification measures can result in material damage.
● We recommend using an uninterruptible power supply (UPS). If you are unsure of the
measures necessary after the device fails, or if a fault cannot be rectified, contact the
Service Center.
After performing repairs, refasten all cable ducts whose cover faces downward with a cable tie.
The cable ties must be located at the same positions as in the delivered state. You will find more
information in "Fastening the cable ducts with cable ties (Page 82)".
NOTICE
Damage caused by an incomplete repair
In the case of damage, several components can have a fault condition. Consequential
damage can occur if the device is recommissioned but the repair work carried out was not
complete.
● Check whether secondary faults have occurred on components which have failed.
Replace the components involved.
Measures in the event of an error
It is not possible to fully test repairs that are carried out on site. Return the defective module
back to the manufacturing plant for repair. The relevant address is available from your Siemens
contact person.
Always enclose the following information:
● Type and serial number
● Time and date of the failure
● Description of the fault profile
Specify what happened when the component failed.
● Operating point, currents and voltages
● Log file with fault messages
Maintenance
9.7 Repair
SINAMICS PERFECT HARMONY GH150 6SL3826
Operating Instructions 05/2020
103
Summary of Contents for SINAMICS PERFECT HARMONY GH150 6SL3826
Page 2: ...19 06 2020 09 25 V14 00 ...
Page 120: ...Spare parts SINAMICS PERFECT HARMONY GH150 6SL3826 120 Operating Instructions 05 2020 ...
Page 124: ...Service Support SINAMICS PERFECT HARMONY GH150 6SL3826 124 Operating Instructions 05 2020 ...
Page 130: ...Quality documents SINAMICS PERFECT HARMONY GH150 6SL3826 130 Operating Instructions 05 2020 ...
Page 135: ......