Terminal Module TM150 is used for sensing and evaluating several temperature sensors.
Terminal Module TM150 is designed to connect a maximum of 12 temperature sensors.
Additional information is provided in document "Supplementary component descriptions
(
https://support.industry.siemens.com/cs/ww/en/view/109768128
)".
3.8.19
Terminal Module TM31 (option G61)
The standard version of the converter includes a Terminal Module TM15. The Terminal Module
is used for the following functions:
● Inclusion of warning and fault messages and control signals.
● Communication with a higher-level control level.
If the number of signals to be monitored is insufficient, the interface can be extended to include
an additional Terminal Module. Additional digital inputs and outputs and two analog inputs and
outputs are available with the TM31. The inputs and outputs are used, for example, for fetching
temperatures.
The TM31 Terminal Module provides the following inputs and outputs:
● 8 digital inputs
● 4 bidirectional digital inputs and outputs
● 2 relay outputs with changeover contact
● 2 analog inputs
● 2 analog outputs
● 1 temperature sensor input (KTY84-130/PTC)
Note
The TM31 must be connected at the plant site.
The default setting of the inputs/outputs is not provided by the factory and must be
undertaken according to the requirements of the respective plant during commissioning.
When the analog inputs and outputs on the optional TM31 are used for communicating with the
control level, additional isolating transformers are available (optional).
3.8.20
Second Terminal Module TM31 (option G62)
Option G62 in conjunction with option G61, includes an additional TM31 Terminal Module.
Description
3.8 Options
SINAMICS PERFECT HARMONY GH150 6SL3826
Operating Instructions 05/2020
47
Summary of Contents for SINAMICS PERFECT HARMONY GH150 6SL3826
Page 2: ...19 06 2020 09 25 V14 00 ...
Page 120: ...Spare parts SINAMICS PERFECT HARMONY GH150 6SL3826 120 Operating Instructions 05 2020 ...
Page 124: ...Service Support SINAMICS PERFECT HARMONY GH150 6SL3826 124 Operating Instructions 05 2020 ...
Page 130: ...Quality documents SINAMICS PERFECT HARMONY GH150 6SL3826 130 Operating Instructions 05 2020 ...
Page 135: ......