r0046
Missing enable signals
Display of the missing enable signals that are preventing the drive control from being commissioned
Bit
Signal name
0-signal
1-signal
18
OFF3 internal enable missing
No
Yes
26
Drive inactive or not operational
No
Yes
r0050
Active command data set (CDS)
Display of the active command data set (Command Data Set, CDS)
Bit
Signal name
0-signal
1-signal
00
CDS effective, bit 0
No
Yes
01
CDS effective, bit 1
No
Yes
02
CDS effective, bit 2
No
Yes
03
CDS effective, bit 3
No
Yes
Further notes can be found in the parameter description of the p0810, p0811, p0812, p0813 and r0836 parameters in the List
Manual.
The command data set selected via binector inputs p0810, p0811, p0812 and p0813 is displayed via r0836.
Diagnostic parameters for digital inputs/outputs
r0721
CU digital inputs terminal actual value
Display of the actual value on the digital inputs
Bit
Signal name
0-signal
1-signal
00
DI 0 (X122.1)
Low
High
01
DI 1 (X122.2)
Low
High
02
DI 2 (X122.3)
Low
High
03
DI 3 (X122.4)
Low
High
04
DI 4 (X132.1)
Low
High
05
DI 5 (X132.2)
Low
High
06
DI 6 (X132.3)
Low
High
07
DI 7 (X132.4)
Low
High
08
DI/DO 8 (X122.7)
Low
High
09
DI/DO 9 (X122.8)
Low
High
10
DI/DO 10 (X122.10)
Low
High
11
DI/DO 11 (X122.11)
Low
High
12
DI/DO 12 (X132.7)
Low
High
13
DI/DO 13 (X132.8)
Low
High
14
DI/DO 14 (X132.10)
Low
High
15
DI/DO 15 (X132.11)
Low
High
If a DI/DO is parameterized as output (p0728.x = 1), then r0721.x = 0 is displayed.
DI: Digital input
DI/DO: Bidirectional digital input/output
Operation
8.6 Fault and system messages
SINAMICS GM150 6SL3835-2LN44-2AA0
170
Operating Instructions Rev.201910281250 MUSTER
Summary of Contents for Sinamics GM150 6SL3835-2LN44-2AA0
Page 2: ...28 10 2019 12 50 V32 00 ...
Page 232: ...Index SINAMICS GM150 6SL3835 2LN44 2AA0 232 Operating Instructions Rev 201910281250 MUSTER ...
Page 233: ......
Page 236: ......
Page 238: ......