![Siemens Sinamics GM150 6SL3835-2LN44-2AA0 Operating And Installation Instructions Download Page 73](http://html.mh-extra.com/html/siemens/sinamics-gm150-6sl3835-2ln44-2aa0/sinamics-gm150-6sl3835-2ln44-2aa0_operating-and-installation-instructions_378208073.webp)
NOTICE
Damage caused by excessively high blow-out pressure
If the blow-out pressure used exceeds 6 bar, the piping and the heat sink can become
damaged.
● Do not exceed the blowout pressure of 6 bar. Avoid pressure surges.
4.5.2
Storing a device
If you are not going to commission the device immediately after delivery, ensure that it is stored
correctly.
Preconditions and preparations
● Store goods only in undamaged packaging. Unpack the goods if the packaging is damaged.
Correctly store the goods corresponding to the type of goods.
● Repair any damage to the packaging before putting the equipment into storage insofar as
this is necessary to ensure proper storage conditions.
General instructions for storage
Wherever possible, store the device in a storage room. The place of storage must satisfy the
following general conditions:
● Select a sufficiently sized dry and horizontal place of storage that is above flood level and
free of vibration (v
eff
≤ 0.2 mm/s).
● The place of storage must be well ventilated as well as free of dust and frost.
– Provide protection against extreme weather conditions.
– Optimum temperatures are between 10° C (50° F) to 50° C (120° F).
– Room temperature should be approx. 10 °C (14 °F) above the outside temperature.
– The temperature may not fall below ‑20 °C (-4 °F).
– For lower temperatures, agree on suitable measures together with Siemens.
– Relative humidity should be less than 60%.
– The floor of the place of storage must be sufficiently strong. Do not exceed maximum
permissible floor load levels or storage compartment load levels.
– The ambient air must not contain any harmful gases.
● Protect the device against shocks and humidity.
Preparations for use
4.5 Storage
SINAMICS GM150 6SL3835-2LN44-2AA0
Operating Instructions Rev.201910281250 MUSTER