Clockwise/counter-clockwise switchover
● Setting "Yes":
In LOCAL mode, left/right switching is possible using the
key.
● Setting "No" (default setting):
The key does not act in LOCAL mode.
In REMOTE mode, the key is always in effect.
For safety reasons, the left/right key is inactive in the default setting. Pumps and fans may
normally be operated only in one rotational direction. In the "Operation" state in LOCAL mode,
the current rotational direction is indicated by an arrow next to the operating mode.
JOG key active (jogging)
● Setting "Yes":
In LOCAL mode, in the "Ready to switch on" state (not in "Operation" state), jogging mode
is possible using the <JOG> key. The speed set in parameter p1058 is approached.
● Setting "No":
The <JOG> key has no effect in LOCAL mode.
The <JOG> key never acts in REMOTE mode.
Save AOP setpoint
● Setting "Yes":
In LOCAL mode, the
and
keys save the set setpoint. The set value is automatically
reset as the setpoint value after the power supply is switched off and on again.
During the switchover from REMOTE to LOCAL mode with the drive switched on (motor
running), the current actual value is set as the AOP setpoint and saved.
During the switchover from REMOTE to LOCAL mode with the drive switched off, the last
saved AOP setpoint is used.
● Setting "No":
In LOCAL mode, after switching the drive off and on, "0" is set as initial value for the AOP
setpoint. "0" is also set as initial value for the AOP setpoint after the power supply has been
switched off and on.
The current value is set as AOP setpoint when switched from REMOTE to LOCAL mode for
activated drive and running motor.
AOP ramp-up time/AOP ramp-down time
The AOP ramp-up time setpoint and the AOP ramp-down time setpoint specify in which time the
<+> and <-> keys change the AOP setpoint.
The ramp-up time acts when the setpoint changes from smaller to larger, i.e positive or negative
values. The ramp-down time acts in the opposite direction.
The times set here act in addition to the ramp-up and ramp-down times set in the drive.
The default setting for the AOP ramp-up time is 20 seconds. The default setting for the AOP
ramp-down time is 30 seconds.
Operation
8.3 Operation via the AOP30 operator panel
SINAMICS GM150 6SL3835-2LN44-2AA0
Operating Instructions Rev.201910281250 MUSTER
119
Summary of Contents for Sinamics GM150 6SL3835-2LN44-2AA0
Page 2: ...28 10 2019 12 50 V32 00 ...
Page 232: ...Index SINAMICS GM150 6SL3835 2LN44 2AA0 232 Operating Instructions Rev 201910281250 MUSTER ...
Page 233: ......
Page 236: ......
Page 238: ......