Replacing the sponge
①
Retaining screws
②
Sponge
Figure 9-33
Replacing the sponge
1. Remove the retaining screws
①
.
2. Take out the sponge
②
.
3. Insert a new sponge and then push it up to the stop of the screw.
4. Reattach the leakage water detection.
Note
Insert the sponge
Make sure that the leakage water measurement is on the bottom pan. The distance between
sponge and bottom pan is then approx. 1 mm.
9.5.8
Replacing fuses
To replace the -F11, -F12 or -F21 fuses, proceed as follows:
1. Disconnect the auxiliary power supply.
2. Remove the defective fuse.
3. Rectify the cause of the fault.
4. Fit the replacement fuse and close the fuse holder.
The order numbers for replacing fuses that have blown can be found in the spare parts list.
Maintenance
9.5 Repair
SINAMICS GM150 6SL3835-2LN44-2AA0
Operating Instructions Rev.201910281250 MUSTER
211