Connecting the motor to the dv/dt filter
Figure 3-11
Connecting the motor to the dv/dt filter
3.6.17
Automatic restart function (option L32)
With option "Automatic restart" (L32), the system automatically restarts when the line supply
fails, irrespective of how long the line supply failure was. Alarms are acknowledged
automatically and the drive is restarted.
Voltage Sensing Module (VSM)
With the "Automatic restart" option, a Voltage Sensing Module VSM10 is integrated in the drive.
The VSM10 acquires the actual voltage values at the medium-voltage level upstream of the
circuit breaker.
When the medium voltage is restored after a power failure, this is detected by the open-loop/
closed-loop controllers via voltage transformers when the input-side circuit breaker has
dropped out. The voltage transformers should be located at the medium-voltage level upstream
of the circuit breaker.
For safety reasons, a time limit between the power failure and the maximum permissible power
restoration time is incorporated to ensure that the drive does not restart in an uncontrolled
manner. As a further warning, an acoustic signal is output when the drive restarts.
You can find further information on the Voltage Sensing Module (VSM10) in Section
"Description of the Components".
Description
3.6 Description of options
SINAMICS GM150 6SL3835-2LN44-2AA0
Operating Instructions Rev.201910281250 MUSTER
53
Summary of Contents for Sinamics GM150 6SL3835-2LN44-2AA0
Page 2: ...28 10 2019 12 50 V32 00 ...
Page 232: ...Index SINAMICS GM150 6SL3835 2LN44 2AA0 232 Operating Instructions Rev 201910281250 MUSTER ...
Page 233: ......
Page 236: ......
Page 238: ......