Alarms, faults and system messages
10.2 Faults
Converter with control units CU250D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
327
Extended settings for faults
Parameter
Description
You can change the fault response of the motor for up to 20 different fault codes:
p2100
Setting the fault number for fault response
Selection of the faults for which the fault response applies
p2101
Setting, fault response
Setting the fault response for the selected fault
You can change the acknowledgment type for up to 20 different fault codes:
p2126
Setting the fault number for the acknowledgment mode
Selection of the faults for which the acknowledgment type should be changed
p2127
Setting, acknowledgment mode
Setting the acknowledgment type for the selected fault
1: Can only be acknowledged using POWER ON
2: IMMEDIATE acknowledgment after removing the fault cause
You can change up to 20 different faults into an alarm or suppress faults:
p2118
Setting the message number for the message type
Selection of the message for which the message type should be changed
p2119
Setting the message type
Setting the message type for the selected fault
1: Fault
2: Alarm
3: No message
You will find details in function diagram 8075 and in the parameter description of the List
Manual.