Advanced commissioning
7.10 Switchover between different settings
Converter with control units CU250D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
273
Table 7- 36 Parameters for switching the drive data sets:
Parameter
Description
p0820[0…n]
Drive data set selection DDS bit 0
If you use several command data sets CDS,
then you must set this parameter for each
CDS. The parameters are assigned to a
CDS through their index:
CDS0: p0820[0], p0821[0]
CDS1: p0820[1], p0821[1]
…
p0821[0…n]
Drive data set selection DDS bit 1
p0826
Motor changeover, motor number
Each drive data set is assigned a motor number:
p0826[0] = motor number for drive data set 0.
…
p0826[3] = motor number for drive data set 3.
If you operate the same motor with different drive data sets, then you must enter the
same motor number in every index of parameter p0826. In this particular case, you
can also switch over between the different drive data sets in operation.
If you operate different motors on one inverter, then you must number the motors in
parameter p0826. In this case, you may only switch over the drive data sets in the
"ready for operation" state with the motor switched-off. The switchover time is ap-
prox. 50 ms.
r0051
Displaying the number of the DDS that is currently effective
For an overview of all the parameters that belong to the drive data sets and can be switched,
see the List Manual.
Table 7- 37 Parameters for copying the drive data sets
Parameter
Description
p0819[0]
Source drive data set
p0819[1]
Target drive data set
p0819[2] = 1
Start copy operation
For more information, see the List Manual (the parameter list and function diagram 8565).