Commissioning
4.7 Data backup with the operator panel and memory card
Frequency inverter
Operating Instructions, 08.10. 2008, t.b.d.
79
Transferring the parameters from the MMC memory card into the frequency inverter (download)
Parameter
Description
P0003 = 3
3: Access level 3
P0010 = 30 30: Parameter transfer
P0803 = 2
2: Start data transfer from the MMC to the EEPROM in the CU. "RDY" LED flashes.
•
If the upload procedure is successful, P0010 and P0803 are set to 0 and the "RDY"
LED lights up.
•
If the download procedure is unsuccessful, F0061 or F0062 is displayed and the
LED "SF" (red) lights up. In this case, make another attempt to transfer data.