Functions
5.10 Technological functions
Frequency inverter
Operating Instructions, 08.10. 2008, t.b.d.
131
Parameterizing a DC & compound brake
Parameter Description
P1230
Enables the DC brake
Enables DC braking via a signal that was used by an external source (BICO). The
function remains active as long as the external signal is active.
P1232=
DC brake current (entered in %)
Defines the strength of the direct current in [%] with respect to the rated motor current
(P0305)
P1233=
Duration of the DC braking (entered in s)
_I_
3
U
%LW
3
3
W
W
W
W
2))
2))2))
21
2))
'&EUDNLQJ
'&EUDNLQJDFWLYH
Defines the duration of DC brake in seconds after an OFF1 or OFF3 command
P1234=
Starting frequency of the DC brake (entered in Hz)
Sets the starting frequency for DC brake.
P1236=
Compound braking (entered in %)
_I_
_I_
IBVHW
IBVHW
IBDFW
IBDFW
W
W
W
W
W
W
L
L
9
'&OLQN
9
'&OLQN
9
'&&RPS
3 9
'&&RPS
෬
෭
෬
3
3ำ9
'&&RPS
෬
U
3
:LWKRXW&RPSRXQGEUDNLQJ
3!
:LWK&RPSRXQGEUDNLQJ
Parameter P1236 defines the direct current superimposed on the motor current after the
DC link voltage threshold has been exceeded.
P1236 = 0 Compound brake disabled
P1236 = 1 - 250 Current level of braking direct current as a % of the rated motor current
(P0305)