Commissioning
4.4 Commissioning with factory settings
Frequency inverter
Operating Instructions, 08.10. 2008, t.b.d.
51
4.4
Commissioning with factory settings
Prerequisites for using the factory settings
In simple applications, commissioning can be carried out just using the factory settings. This
section explains what prerequisites must be fulfilled for this purpose and how they are
fulfilled.
1.
The frequency inverter and motor must match one another; otherwise you must perform a
complete
quick commissioning (see Chapter 'Quick commissioning').
2.
The binary and analog inputs must be connected in accordance with the wiring example
(see Section 'Wiring example').
3.
You then have to "tell" the converter the following,
–
the source of its commands:
- from an 0perator panel,
- from the digital inputs
- from the fieldbus interface
You can change this
command source using parameter P0700 if the factory setting is
not appropriate for your application.
–
where it gets its speed setpoint (setpoint source)
- from an analog input (analog setpoint)
- as fixed frequency from a digital input
- from the fieldbus interface
You can change this
frequency setpoint source using parameter P1000 if the factory
setting is not appropriate for your application.