Functions
5.10 Technological functions
Frequency inverter
Operating Instructions, 08.10. 2008, t.b.d.
141
P1210 = 4: Automatic restart following power failure, no further startup attempts
When P1210 = 4, an automatic restart is only carried out if fault F30003 has also occurred on the
Power Module, a high signal is present at the binector input P1208[1], or if fault F06200 has occurred
when an infeed drive object (x_Infeed) is used. If additional faults are present, these are also
acknowledged and, if this is successful, the start attempt is continued. If the 24 V power supply for
the CU fails, this is interpreted as a power failure.
P1210 = 6: Automatic restart after any fault with further start attempts
When P1210 = 6, an automatic restart is carried out following any fault or when P1208[0] = 1. If the
faults occur one after the other, the number of start attempts can be defined by means of P1211.
Time monitoring can be set with P1213.
Commissioning
1.
Activate the "automatic restart" function via P1210 and, if necessary, the "flying restart"
function via P1200.
2.
Set the number of start attempts via P1211.
3.
Set the waiting times via P1212 and P1213.
4.
Make sure that this functions properly.