Technical data
8.4 Technical data, PM240 Power Modules
Frequency inverter
Operating Instructions, 08.10. 2008, t.b.d.
229
Table 8- 4
PM240 Frame Size F
Order No., unfiltered 6SL3224-0BE34-
5AA0
6SL3224-0BE35-
5AA0
6SL3224-0BE37-
5AA0
6SL3224-0BE38-
8UA0
6SL3224-0BE41-
1UA0
Order No., filtered
6SL3224-0BE34-
5UA0
6SL3224-0BE35-
5UA0
6SL3224-0BE37-
5UA0
-
-
Power rating for HO
base load
45 kW / 60 PS
55 kW / 75 PS
75 kW / 100 PS
90 kW / 125 PS
110 kW / 150 PS
Input current for HO
base load
108 A
132 A
169 A
205 A
235 A
Output current for
HO base load
90 A
110 A
145 A
178 A
205 A
Input current for LO
base load
129 A
168 A
204 A
234 A
284 A
Output current for LO
base load
110 A
145 A
178 A
205 A
250 A
Fuse
160 A
200 A
250 A
250 A
315 A
Heat loss
1.5 KW
2.0 KW
2.4 KW
2.4 kW
2.5 kW
Cooling air
requirement
150 l/s / 320 CFM 150 l/s / 320 CFM 150 l/s / 320 CFM 150 l/s / 320 CFM 150 l/s / 320 CFM
Cable cross-section
for line and motor
connections
35 … 120 mm
2
2 … 4/0 AWG
35 … 120 mm
2
2 … 4/0 AWG
35 … 120 mm
2
2 … 4/0 AWG
35 … 120 mm
2
2 … 4/0 AWG
35 … 120 mm
2
2 … 4/0 AWG
Weight
Filtered: 52 kg /
115 lb; unfiltered:
36 kg / 80 lb
Filtered: 52 kg /
115 lb; unfiltered:
36 kg / 80 lb
Filtered: 52 kg /
115 lb; unfiltered:
36 kg / 80 lb
39 kg / 90 lb
39 kg / 90 lb
Table 8- 5
PM240 Frame Size G
Order No.
6SL3224-0BE41-3UA0
6SL3224-0BE41-6UA0
6SL3224-0BE42-0UA0
Power rating for HO
base load
132 kW / 177 PS
160 kW / 215 PS
200 kW / 268 PS
Input current for HO
base load
245 A
297 A
354 A
Output current for
HO base load
250 A
302 A
370 A
Input current for LO
base load
297 A
354 A
442 A
Output current for LO
base load
302 A
370 A
477 A
Fuse
355 A
400 A
630 A
Heat loss
3.9 KW
4.4 KW
5.5 KW
Cooling air
requirement
360 l/s / 760 CFM
360 l/s / 760 CFM
360 l/s / 760 CFM
Cable cross-section
for line and motor
connections
95 ... 240 mm
2
3/0 ... 600 AWG
120 ... 240 mm
2
4/0 ... 600 AWG
185 ... 240 mm
2
6/0 ... 600 AWG
Weight
176 kg / 388 lb
176 kg / 388 lb
176 kg / 388 lb