9. Connect the power cable to the following terminals as shown in the terminal diagram.
– CE version: L1, N and PE at terminals
⑨
– UL version: L1 and N at the rotary disconnection device
⑩
, PE at terminal
⑨
10.Connect all of the cables at the terminal block
⑧
as shown in the terminal diagram.
11.Tighten the cable glands
⑤
correctly so that the degree of protection of the connectivity
module is guaranteed.
12.Attach the shield connection clamp to the terminal block
⑧
. Carefully ensure that all of the
cables are not strained.
13.Close the miniature circuit breaker
①
.
14.Close the sensor box door. For the UL version of the connectivity module, follow the
instructions provided in Chapter Only UL version: Opening and closing the sensor box door
(Page 25).
Maintenance
9.7 Replacing connectivity module components
50
Operating Instructions, 06/2020