14.Under "Static > SM1281 Config", set the start value of parameter "S7lead?" to TRUE.
15.Load the software to the device.
When requested to do so, enter the password specified under step 8 of the previous handling
instructions (restoring the configuration for CPU SIMATIC S7-1212C DC/DC/DC).
A note to log out is displayed in the web interface.
16.In the web interface, confirm the login with "OK".
After approximately 1 minute, the operating mode switches to "RUN: X-Tools".
17.Once the operating mode has switched to "RUN: X-Tools", withdraw the LAN cable from the
LAN connection
②
.
18.Reconnect the internal LAN cable to the LAN connection
②
.
19.Close the sensor box. For the UL version of the connectivity module, follow the instructions
provided in ChapterOnly UL version: Opening and closing the sensor box door (Page 25).
9.9
Changing the password for X-Tools
Precondition
• A Remote Desktop Connection has been established from the local service PC to the IPC.
• The password (Page 19) for X-Tools is known.
Procedure
1. Open X-Tools on the IPC.
2. Open the "Servers" element in the "Main Management System" configuration window.
Maintenance
9.9 Changing the password for X-Tools
56
Operating Instructions, 06/2020
Summary of Contents for SIMOTICS CONNECT 600
Page 2: ......
Page 8: ...Introduction 1 2 Naming convention 6 Operating Instructions 06 2020 ...
Page 14: ...Safety instructions 2 6 Security recommendations 12 Operating Instructions 06 2020 ...
Page 34: ...Connection 6 3 Connecting the IPC 32 Operating Instructions 06 2020 ...
Page 42: ...Operation 8 1 Data evaluation with SIDRIVE IQ 40 Operating Instructions 06 2020 ...
Page 72: ...Service support A 1 Product support 70 Operating Instructions 06 2020 ...
Page 79: ......