Interface module
7.4 Interface module SB70
SIMATIC TDC hardware
198
System Manual, 08/2017, A5E01114865-AL
Voltage supply on SIMATIC side
The SIMATIC TDC voltage supply is fed to terminal X3:
Terminal X3
Voltage on SIMATIC TDC side
1P
1M
+24 V
0 V
Connect the cables using accessory kit SM11 "Power supply connector for interface
modules" (article number: 6DD1680-0BB0)
The maximum conductor cross-section at terminal X3 is 2.5 mm².
Note
When wiring the supply voltage, observe the “Installation and EMC Directives” chapter in the
User Manual.
WARNING
Isolation
Safe electrical isolation is guaranteed only between the inputs and outputs
The system side (rack including 24V power supply) is safely isolated from hazardous
voltages on plant side (8 output signals).
The output circuits are only isolated galvanically.
The output circuits on plant side are only isolated galvanically. Circuits consisting of
combinations of safety extra-low voltage and hazardous voltages are not allowed.
Green LED
The voltage supply on SIMATIC TDC side is indicated by a green LED (P).
Red LED
The supply voltage on SIMATIC TDC side (1P, 1M) is short-circuited (fault).
Test socket
The SIMATIC TDC supply voltage is available on the double test socket X5 (G; +):
Double test socket X5
Voltage SIMATIC side
+ (1P of X3)
G (1M of X3)
+24 V
0 V