Rack
3.2 Rack UR5213 (6DD1682-0CH2)
SIMATIC TDC hardware
56
System Manual, 08/2017, A5E01114865-AL
3.2.4
Status and fault displays
Table 3- 2
Status displays for UR5213
LED
Display
Rack state
POWER
(green or red)
green is on fault-free operation
red is on
fault (refer to voltage monitoring)
FAN FAIL
(red)
Off
fault-free operation
On
fault (at least one fan has failed)
SYSFAIL
(red)
Off
fault-free operation
On
System was stopped
SHUTDOWN Mode
(yellow)
On
Shutdown on failure of two fans (corresponds to the OFF posi-
tion of switch S1.4)
Flashing
Shutdown on failure of one fan (corresponds to the ON position
of switch S1.4)
3.2.5
Power supply
Mains connection
Mains is connected to the 3-pin screw terminal block on the right side of the power supply
unit.
Note
Always use the integrated strain relief for the mains cable on the 3-pin screw terminal block.
The pin assignment is printed onto the front panel.
Input voltage
85–264 V AC
Test voltage
Primary ↔ PE
1350 V AC
Power consumption
800 W (apparent power approx. 835 VA)
Conductor cross-section
3x1.5 mm2 (stranded wires dressed with wire end ferrules with
ISO insulating collars)
External fuse
(dimensioning)
In = 9 A
Is = <40 A (inrush peak)
The power supply is equipped with an internal 20 A fuse. This
means that only the mains supply has to be fused. It is recom-
mended to use a standard 16 A thermo magnetic circuit-breaker
(B characteristic).
Alternatively, a slow-acting fuse may be used.
Note
A mains disconnect unit must be provided during installation of the rack.