Rack
3.1 Rack UR6021 (6DD1682-0CH3)
SIMATIC TDC hardware
System Manual, 08/2017, A5E01114865-AL
51
3.1.12
Technical specifications
Article number
Rack UR6021
6DD1682-0CH3
General data
Safety
EN 61131-2
Degree of protection
IP 20
Protection class
Protection class 1 with PE/ground conductor
Storage temperatures
-40 °C to +70 °C
Operating temperatures
0 °C to +60 °C
Relative air humidity
5 % to 95 %, no condensation
Atmospheric pressure
Operation: 1080 hPa to 795 hPa
Storage: 1080 hPa to 660 hPa
Power input
Rated input voltage
•
Rated value
•
Permissible range
•
120 V AC to 230 V AC
110 V DC to 220 V DC
•
85 V AC to 264 V AC (wide-range input)
93.5 V DC to 253 V DC
Rated input current
•
At 120 V AC
•
At 230 V AC
•
At 110 V DC
•
At 220 V DC
•
6.7 A
•
3.5 A
•
7.3 A
•
3.7 A
Max. inrush current
< 40 A
Line frequency
•
Rated value (AC)
(DC)
•
Permissible range
•
50/60 Hz
(0 Hz)
•
47-63 Hz
Power factor
EN 61000-3-2
Pollution degree
2
Overvoltage category
II
Power failure backup
min. 20 ms
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China
+86-755-8660-6182