Technical specifications
A.5 Thermocouple and RTD expansion modules (EMs)
S7-200 SMART
System Manual, V2.3, 07/2017, A5E03822230-AF
753
Model
EM AT04 AI 4 x 16 bit TC
Module update time
See Filter selection table.
Cold junction error
±1.5 °C
Cable length (meters)
100 m to sensor max.
Wire resistance
100 Ω max.
Table A- 118 Diagnostics
Model
EM AT04 AI 4 x 16 bit TC
Overflow/underflow
1
Yes
Wire break (current mode only)
2
Yes
24 V DC low voltage
1
Yes
1
The overflow, underflow and low voltage diagnostic alarm information will be reported in the analog data values even if
the alarms are disabled in the module configuration.
2
When wire break alarm is disabled and an open wire condition exists in the sensor wiring, the module may report ran-
dom values.