Technology functions
3.2 Pulse generators
CPU 1512C-1 PN (6ES7512-1CK01-0AB0)
Manual, 12/2017, A5E40898741-AA
55
Setting and changing the pulse on-load factor
OUTPUT_VALUE assigns the on-load factor for the current period duration. You select the
range of the field OUTPUT_VALUE of the control interface with the "Output format"
parameter.
●
Output format per 100: Value range between 0 and 100
Pulse duration = (OUTPUT_VALUE/100) x period duration.
●
Output format 1/1000: Value range between 0 and 1 000
Pulse duration = (OUTPUT_VALUE/1 000) x cycle duration.
●
Output format 1/10000: Value range between 0 and 10 000
Pulse duration = (OUTPUT_VALUE/10 000) x cycle duration.
●
Output format "S7 analog output": Value range between 0 and 27,648
Pulse duration = (OUTPUT_VALUE/27 648) x period duration.
You assign OUTPUT_VALUE directly via the control program. A new OUTPUT_VALUE is
applied at the output when the next rising edge occurs.
Setting and changing the period duration
●
Permanent updating
The period duration is permanently controlled via the control interface. The MODE_SLOT
bit must be set ("1" means permanent updating); LD_SLOT must be set to value 1 ("1"
means period duration). Set the period value in the field SLOT. The unit is always a
microsecond.
–
High-speed output activated: between 10
μs and 10
000 000
μs (10 s) in the field
SLOT
–
High-speed output deactivated: between 100
μs and 10
000 000
μs (10
s) in the field
SLOT
–
Standard output (100 Hz output): between 10 000 µs (10 ms) and 10 000 000 µs
(10 s) in the field SLOT
●
Individual updating
Set the period duration in the configuration parameters. Alternatively, execute an
individual updating via the control interface. MODE_SLOT must be deleted ("0" means
individual updating); LD_SLOT must be set to value 1 ("1" means period duration). Set
the period duration value in the field SLOT. The unit is always a microsecond.
–
High-speed output activated: between 10
μs and 10
000 000
μs (10
s) in the
parameters
–
High-speed output deactivated: between 100
μs and 10
000 000
μs (10
s) in the
parameters
–
Standard output (100 Hz output): between 10 000 µs (10 ms) and 10 000 000 µs
(10 s) in the parameters
The new period duration is applied at the next rising edge of the output.