Technical specifications
CPU 1512C-1 PN (6ES7512-1CK01-0AB0)
160
Manual, 12/2017, A5E40898741-AA
Article number
6ES7512-1CK01-0AB0
Accuracy
–
Frequency measurement
100 ppm; depending on measuring interval and
signal evaluation
–
Cycle duration measurement
100 ppm; depending on measuring interval and
signal evaluation
–
Velocity measurement
100 ppm; depending on measuring interval and
signal evaluation
Potential separation
Potential separation digital inputs
•
between the channels
No
•
between the channels, in groups of
16
Potential separation digital outputs
•
between the channels
No
•
between the channels, in groups of
16
Potential separation channels
•
between the channels and backplane bus
Yes
•
Between the channels and load voltage L+ No
Isolation
Isolation tested with
707 V DC (type test)
Ambient conditions
Ambient temperature during operation
•
horizontal installation, min.
0 °C
•
horizontal installation, max.
60 °C; Note derating data for onboard I/O in the
manual. Display: 50 °C, at an operating tempera-
ture of typically 50 °C, the display is switched off
•
vertical installation, min.
0 °C
•
vertical installation, max.
40 °C; Note derating data for onboard I/O in the
manual. Display: 40 °C, at an operating tempera-
ture of typically 40 °C, the display is switched off
Ambient temperature during stor-
age/transportation
•
min.
-40 °C
•
max.
70 °C
Configuration
Programming
Programming language
–
LAD
Yes
–
FBD
Yes
–
STL
Yes
–
SCL
Yes
–
GRAPH
Yes
Summary of Contents for Simatic S7-1500 CPU 1512C-1 PN