Technical specifications
CPU 1512C-1 PN (6ES7512-1CK01-0AB0)
Manual, 12/2017, A5E40898741-AA
157
Article number
6ES7512-1CK01-0AB0
S7 message functions
Number of login stations for message func-
tions, max.
32
Program alarms
Yes
Number of configurable program alarms
5 000
Number of simultaneously active program
alarms
•
Number of program alarms
300
•
Number of alarms for system diagnostics
100
•
Number of alarms for motion technology
objects
80
Test commissioning functions
Joint commission (Team Engineering)
Yes; Parallel online access possible for up to 5
engineering systems
Status block
Yes; Up to 8 simultaneously (in total across all
ES clients)
Single step
No
Number of breakpoints
8
Status/control
•
Status/control variable
Yes
•
Variables
Inputs/outputs, memory bits, DBs, distributed
I/Os, timers, counters
•
Number of variables, max.
–
of which status variables, max.
200; per job
–
of which control variables, max.
200; per job
Forcing
•
Forcing, variables
Peripheral inputs/outputs
•
Number of variables, max.
200
Diagnostic buffer
•
present
Yes
•
Number of entries, max.
1 000
–
of which powerfail-proof
500
Traces
•
Number of configurable Traces
4; Up to 512 KB of data per trace are possible
Interrupts/diagnostics/status information
Alarms
•
Diagnostic alarm
Yes
•
Hardware interrupt
Yes
Summary of Contents for Simatic S7-1500 CPU 1512C-1 PN