Properties of the analog inputs
The 5 inputs of the analog on-board I/O module have the following properties:
Property
Description
Additional information
Resolution: 16 bits includ-
ing sign
A CPU processes information exclusively in digital
format. An ADC (analog-to-digital converter) integrated
into the analog on-board I/O module therefore converts
the analog value into a bit pattern. For the CPU, this
conversion always returns a 16-bit word for SIMATIC
products. The ADC used digitalizes the analog signal
and approximates its value with a stepped curve. The
resolution specifies the number of increments of the
analog value along this stepped curve here.
•
Chapter Analog value pro-
cessing
•
Analog value processing function
manual
http://support.automation.sieme
Integrated types of meas-
uring
Controllers are only capable of processing analog val-
ues in the form of bit patterns. For this purpose, trans-
ducers which can be connected to the analog module
measure physical variables such as pressure or tem-
perature. This analog value is measured by the analog
input module in the form of the measurement types
current, voltage or resistance. The analog on-board I/O
module supports the following measurement types on
the following channels.
•
Voltage measurement type can be set individually
for channel 0 to 3
•
Current measurement type can be set individually
for channel 0 to 3
•
Resistor measurement type can be set for channel 4
•
Thermal resistor measurement type can be set for
channel 4
Configurable diagnostics The analog on-board I/O module can diagnose errors.
The module reports the diagnosed state to the CPU
using a diagnostics error interrupt. Different types of
diagnostics are available that you can parameterize
channel-granularly.
Chapter Parameters of the analog
on-board I/O (Page 122)
Hardware interrupt
You can react to process events (such as nega-
tive/positive exceeding of specific limits) through the
configuration of a hardware interrupt. Hardware inter-
rupts can be parameterized channel-granularly.
•
Chapter Parameters of the ana-
log on-board I/O (Page 122)
•