Application and functions
1.2 Properties of the CP
CP 1243-8 IRC
12
Operating Instructions, 02/2018, C79000-G8976-C385-03
Supported telecontrol protocols
Depending on the firmware version the CP supports the following protocols.
●
Firmware version V2.1
–
SINAUT ST7
●
Firmware version V3
–
SINAUT ST7
–
DNP3
–
IEC 60870-5
You will find the supported transmission protocols and network types in the section
Communications services (Page 14).
Application
The CP can be used in the following systems:
●
SINAUT ST7 system
In existing SINAUT systems in which the ST7 protocol is used, the CP can be used with
the functions of TIM 3V-IE Advanced.
If used for this purpose note the instructions below on configuration.
●
New ST7 systems
New systems with S7-1200 stations in which the ST7 protocol is used.
●
Existing DNP3 or IEC systems
In existing systems in which the DNP3 or the IEC protocol is used, the CP can be used
as the communications processor of the SIMATIC S7-1200.
Communications partners
The interfaces of the CP support the network node type "station". A master station can be
connected as the communications partner of the CP. When using the ST7 protocol, a master
station or node station can be connected.
Depending on the firmware version of the CP, a master station with one of the following
applications can be connected.
●
Firmware version V2.1
The following master station applications are possible:
–
SINAUT ST7cc
–
SINAUT ST7sc
–
SIMATIC PCS 7 / WinCC TC
–
SIMATIC WinCC OA
–
A SINAUT master station or node station