Configuration
4.16 Security
CP 1243-8 IRC
Operating Instructions, 02/2018, C79000-G8976-C385-03
117
Configuration of SINEMA Remote Connect
Importing your own certificate
1.
Navigate to the parameter group "Security > Certificate manager".
2.
Open the certificate selection with a double-click on the first free table row of the local
certificate manager.
3.
Select the CA certificate of SINEMA RC - Server.
Then navigate to the parameter group "Security > VPN".
VPN > General
1.
Activate VPN
2.
For the parameter "VPN connection type", select the option "Automatic OpenVPN
configuration via SINEMA Remote Connect Server" if you wish to use communication via
SINEMA Remote Connect.
If you select "Internet Key Exchange (IKE) ...", you can use communication via IPsec
tunnels.
SINEMA Remote Connect Server
Enter the address and port number of the server.
Server Verification
Here you select the authentication method of the communication module during connection
establishment.
●
CA Certificate
Under "CA certificate" select the CA certificate from SINEMA RC - Server that was
previously imported and activated in the local certificate manager.
The module generally checks the CA certificate of the server and its validity period. The
two options cannot be changed.
●
Fingerprint
When you select this authentication method, you enter the fingerprint of the server
certificate of SINEMA RC - Server.
Authentication
●
Device ID
Enter the device ID generated for the module in SINEMA RC.
●
Device password
Enter the device password of the module configured in SINEMA RC.
Max. number of characters: 127