5-3
Distributed I/O System DP/ASi Link
EWA 4NEB 710 6055-02b
5.1
Configuring – for Example with COM ET 200 Windows (Version 2.0
or Later)
In the following you will find a description of the method by which you can
integrate the DP/ASi link into the PROFIBUS-DP using COM ET 200
Windows (version 2.0 or later). You will find additional information about
the different steps in the integrated online Help of COM ET 200 Windows.
1. Open the worksheet with the DP master to which you wish to connect the
DP/ASi link.
2. Click in the Slaves window on ASi . As soon as you exit from the Slaves
window, the mouse pointer changes its appearance.
3. Click the mouse on the point of the user interface at which you wish to
insert the DP/ASi link.
4. Select the slave station number from the list box.
5. Click OK to confirm your selection.
You can configure or assign parameters to the DP/ASi link even at this
stage by clicking once on Configure... or Parameterize....
6. To insert further DP slaves, repeat steps 3 to 5 above.
Once you have inserted the DP/ASi link in the PROFIBUS-DP, you have to
configure it. Proceed in the following order:
1. Click on Configure...
2. Select an ASi slave number. Double-click in the I/O field of the slave
number to go to a new input window.
3. Select the I/O code of your ASi slave from the list.
4. You can now edit the ID code and the parameter value of the ASi slave
you selected, the default values both being 15. If the ID code of your ASi
slave is not 15, you have to enter the corresponding value here.
In the case of a DP standard master of limited configuration – for ex-
ample, S5-95U – step 4 cannot be performed.
5. Set the base address of the SIMATIC address assignment. You have to set
the base address separately for inputs and outputs only once for every
DP/ASi link.
6. Assign the corresponding address assignment to the ASi slave using
Auto addr.
You do not obtain the final address assignment until you have
configured all the ASi slaves.
7. For all the other ASi slaves you wish to connect to the DP/ASi link, re-
peat steps 2 to 6 above with the exception of step 5.
Method
Configuring
Configuring the DP/ASi Link
Summary of Contents for SIMATIC Distributed I/O System DP/ASi Link
Page 6: ...vi Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Preface ...
Page 18: ...1 6 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Overview ...
Page 26: ...2 8 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b ASi Basics ...
Page 72: ...5 12 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Configuring the DP ASi Link ...
Page 116: ...B 2 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b I O Code ...
Page 128: ...C 12 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Parameterization Message ...
Page 148: ...Index 6 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Index ...