4-14
Distributed I/O System DP/ASi Link
EWA 4NEB 710 6055-02b
In certain cases the station number in the EEPROM of the DP/ASi link has to
be reset. Proceed in the following order:
Step
Action
1
Turn off the power supply for the DP/ASi link.
2
Turn switch 8 on the DIP switch block to OFF.
3
Turn on the power supply for the DP/ASi link and then turn it off
after automatic start-up of the DP/ASi link. Start-up is aborted
with an error message. The station number is reset to 126.
4
Turn switch 8 on the DIP switch block to ON.
5
Turn on the power supply for the DP/ASi link.
6
Set the correct station number again with the ET 200 Handheld or
by means of the DP master.
Resetting station
numbers
Installing and Wiring the DP/ASi Link
Summary of Contents for SIMATIC Distributed I/O System DP/ASi Link
Page 6: ...vi Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Preface ...
Page 18: ...1 6 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Overview ...
Page 26: ...2 8 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b ASi Basics ...
Page 72: ...5 12 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Configuring the DP ASi Link ...
Page 116: ...B 2 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b I O Code ...
Page 128: ...C 12 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Parameterization Message ...
Page 148: ...Index 6 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Index ...