8-20
Distributed I/O System DP/ASi Link
EWA 4NEB 710 6055-02b
8.2.8
Second Station Diagnosis with the S7/ M7 DP Master
The second part of the station diagnosis is contained in bytes 17 to 23.
The contents of bytes 17 to 19 are shown in Table 8-17.
Table 8-17
Structure of bytes 17 to 19 in diagnostic message
Byte
Con-
tents
Contents
17
60
H
Channel type (channel module)
18
00
H
Length of overall diagnostic information per channel
19
20
H
Number of channel modules
Diagnostic bytes 20 to 23 indicate an ASi slave failure. In Table 8-18, you
will see the assignment of the different bits to the ASi address.
Erroneous ASi slaves are marked ”1”.
Table 8-18
Assignment of the ASi address to bit positions, bytes 20 to 23
Byte
Bit (Corresponds to ASi Address)
7
6
5
4
3
2
1
0
20
7
6
5
4
3
2
1
1
21
15
14
13
12
11
10
9
8
22
23
22
21
20
19
18
17
16
23
31
30
29
28
27
26
25
24
1
This position is not assigned.
Area
Contents
ASi slave diagno-
sis
Diagnostics and Error Handling
Summary of Contents for SIMATIC Distributed I/O System DP/ASi Link
Page 6: ...vi Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Preface ...
Page 18: ...1 6 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Overview ...
Page 26: ...2 8 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b ASi Basics ...
Page 72: ...5 12 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Configuring the DP ASi Link ...
Page 116: ...B 2 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b I O Code ...
Page 128: ...C 12 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Parameterization Message ...
Page 148: ...Index 6 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Index ...