C-7
Distributed I/O System DP/ASi Link
EWA 4NEB 710 6055-02b
In Table C-7 you will find the assignment of the ASi addresses to the byte
numbers within the parameterization message.
Table C-7
Assignment of parameterization data of ASi slaves to byte numbers of
parameterization message
Parameterization Data for ASi Slave with
ASi Address
... Assigned to Bytes
1
16 to 19
2
20 to 23
3
24 to 27
4
28 to 31
5
32 to 35
31
136 to 139
The way in which you determine the value of an input or output byte is
shown in the table below. ASi slave No. 4, as defined in Fig. C-1, is used in
the example.
Step
Action
Explanation
1
Byte number:
1
Bit number: 0
Take the byte number (1) and the bit num-
ber (0) from the address space template (refer
to Fig. C-1).
2
1
0
0
0
0
0
0
0
0
2
0
4
Bit No.
Convert the byte number into a 5-digit binary
number and the bit number into a 3-digit
binary number. You will obtain the byte num-
ber 00001
B
and the bit number 000
B
.
3
1
0
0
0
0
0
0
0
0
2
3
7
Bit No.
Merge the two binary numbers. The bit num-
ber is sorted into the position of bits 0 to 2 and
the byte number into the position of bits 3 to 7.
4
0
0
0
1
0
0
0
0
Divide the eight bits you obtain at the center
into two groups of four bits.
5
0
H
8
H
Convert both of the two groups into a hexade-
cimal number.
6
08
H
Unite the two hexadecimal numbers.
Address
assignment
Example
Parameterization Message
Summary of Contents for SIMATIC Distributed I/O System DP/ASi Link
Page 6: ...vi Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Preface ...
Page 18: ...1 6 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Overview ...
Page 26: ...2 8 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b ASi Basics ...
Page 72: ...5 12 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Configuring the DP ASi Link ...
Page 116: ...B 2 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b I O Code ...
Page 128: ...C 12 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Parameterization Message ...
Page 148: ...Index 6 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Index ...