Analog electronic modules
4.2 Analog value representation
ET 200S
Manual, Edition 10/2005, A5E00514527-01
4-11
Measuring range for thermocouple type J
Table 4-17 SIMATIC S7 format: Measuring range Type J in °C and °F
Units
Units
Type J in °C
Decimal Hexadecima
l
Type J in °F
Decimal
Hexadeci
mal
Range
> 1450.0
32767
7FFF
H
> 2642.0
32767
7FFF
H
Overflow
1450.0
:
1200.1
14500
:
12010
38A4
H
:
2EEA
H
2642.0
:
2192.1
26420
:
21921
6734
H
:
55A1
H
Overshoot range
1200.0
:
-210.0
12000
:
-2100
2EE0
H
:
F7CC
H
2192.0
:
-346.0
21920
:
-3460
55A0
H
:
F27C
H
Rated range
< -210.0
- 32768
8000
H
< -346.0
- 32768
8000
H
Underflow
Measuring range for thermocouple type K
Table 4-18 SIMATIC S7 format: Measuring range Type K in °C and °F
Units
Units
Type K in °C
Decimal Hexadecima
l
Type K in °F
Decimal
Hexadeci
mal
Range
> 1622.0
32767
7FFF
H
> 2951.6
32767
7FFF
H
Overflow
1622.0
:
1372.1
16220
:
13721
3F5C
H
:
3599
H
2951.6
:
2501.7
29516
:
25062
734C
H
:
61B9
H
Overshoot range
1372.0
:
-270.0
13720
:
-2700
3589
H
:
F574
H
2501.6
:
-454.0
25061
:
-4540
61B8
H
:
EE44
H
Rated range
< -270.0
- 32768
8000
H
< -454.0
- 32768
8000
H
Underflow
Measuring range for thermocouple type L
Table 4-19 SIMATIC S7 format: Measuring range Type L in °C and °F
Units
Units
Type L in °C
Decimal Hexadecima
l
Type L in °F
Decimal
Hexadeci
mal
Range
> 1150.0
32767
7FFF
H
> 2102.0
32767
7FFF
H
Overflow
1150.0
:
900.1
11500
:
9001
2CEC
H
:
2329
H
2102.0
:
1652.1
21020
:
16521
521C
H
:
4089
H
Overshoot range
900.0
:
-200.0
9000
:
-2000
2328
H
:
F830
H
1652.0
:
-328.0
16520
:
-3280
4088
H
:
F330
H
Rated range
< -200.0
-32768
8000
H
< -328.0
-32768
8000
H
Underflow